110
Learning Basic Features
Code
Description
In.53 I2 Curr x1
In.56 I2 Perc y2
Configures the gradient level and off-set value of the output frequency.
[Gradient and off-set configuration based on output frequency]
Setting a Frequency Reference with Input Voltage
(Terminal I2)
Set and modify a frequency reference using input voltage at I2 (V2) terminal by setting SW2
to V2. Set the Frq (Frequency reference source) code in the Operation group to 4 (V2) and
apply 012V input voltage to I2 (=V2, Analog current/voltage input terminal). Codes In.3547
will not be displayed when I2 is set to receive current input (Frq code parameter is set to 5).
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
Operation
Frq
Frequency
reference source
Freq Ref Src
4
V2
012
-
In
35
V2 input display
V2 Monitor
0.00
0.0012.00
V
37
V2 input filter time
constant
V2 Filter
10
010000
ms
38
Minimum V2 input
voltage
V2 Volt x1
0.00
0.0010.00
V
39
Output% at
minimum V2
voltage
V2 Perc y1
0.00
0.00100.00
%
40
Maximum V2 input
voltage
V2 Volt x2
10.00
0.0010.00
V
41
Output% at
maximum V2
V2 Perc y2
100.00
0.00100.00
%