147
Learning Basic Features
Code
Description
In.90 DI Status
Display the configuration of each contact. When a segment is configured as
A terminal using dr.87, the On condition is indicated by the top segment
turning on. The Off condition is indicated when the bottom segment is turned
on. When contacts are configured as B terminals, the segment lights behave
conversely. Terminals are numbered P1P7, from right to left.
Type
A terminal setting (On)
A terminal setting (Off)
Keypad
LCD
keypad
4.21 P2P Setting
The P2P function is used to share input and output devices between multiple inverters. To
enable P2P setting, RS-485 communication must be turned on .
Inverters connected through P2P communication are designated as either a master or
slaves . The Master inverter controls the input and output of slave inverters. Slave inverters
provide input and output actions. When using the multi-function output, a slave inverter can
select to use either the master inverters output or its own output. When using P2P
communication, first designate the slave inverter and then the master inverter. If the master
inverter is designated first, connected inverters may interpret the condition as a loss of
communication.
Master Parameter
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
CM
95
P2P
Communication
selection
Int 485 Func
1
P2P Master
03
-
US
80
Analog input1
P2P In V1
0
012,000
%
81
Analog input2
P2P In I2
0
-12,000
12,000
%
82
Digital input
P2P In DI
0
00x7F
bit
85
Analog output
P2P Out AO1
0
010,000
%
88
Digital output
P2P Out DO
0
00x03
bit