Linear V/F Pattern Setting Details
Sets the base frequency. A base frequency is the inverter’s output frequency
when running at its rated voltage. Refer to the motor’s rating plate to set this
parameter value.
Sets the start frequency. A start frequency is a frequency at which the
inverter starts voltage output. The inverter does not produce output voltage
while the frequency reference is lower than the set frequency. However, if a
deceleration stop is made while operating above the start frequency, output
voltage will continue until the operation frequency reaches a full-stop (0Hz).
Square Reduction V/F pattern Operation
Square reduction V/F pattern is ideal for loads such as fans and pumps. It provides non-
linear acceleration and deceleration patterns to sustain torque throughout the whole
frequency range.
Square Reduction V/F pattern Operation - Setting Details
Sets the parameter value to 1(Square) or 3(Square2) according to the
load’s start characteristics.
The inverter produces output voltage proportional to
1.5 square of the operation frequency.
The inverter produces output voltage proportional to
2 square of the operation frequency. This setup is
ideal for variable torque loads such as fans or
pumps.