Learning Basic Features
Setting a Frequency Reference via RS-485 Communication
Control the inverter with upper-level controllers, such as PCs or PLCs, via RS-485
communication. Set the Frq (Frequency reference source) code in the Operation group to 6
(Int 485) and use the RS-485 signal input terminals (S+/S-/SG) for communication. Refer to
7 RS-485 Communication Features on page 273.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
Operation
Frq
Frequency reference
source
Freq Ref Src
6
Int 485
012
-
CM
01
Integrated RS-485
communication
inverter ID
Int485 St ID
-
1
1250
-
02
Integrated
communication
protocol
Int485 Proto
0
ModBus
RTU
02
-
1
Reserved
2
LS Inv 485
03
Integrated
communication
speed
Int485 BaudR
3
9600 bps
07
-
04
Integrated
communication
frame configuration
Int485 Mode
0
D8/PN/S1
03
-
1
D8/PN/S2
2
D8/PE/S1
3
D8/PO/S1