Table of Functions
338
8.8 Communication Function group (PARCM)
In the following table, the data shaded in grey will be displayed when a related code has
been selected.
SL: Sensorless vector control (dr.09) , I IM Sensorless, P PM Sensorless
*O/X: Write-enabled during operation, 7/L/A: Keypad/LCD keypad/Common
Code
Comm.
Address
Name
LCD
Display
Setting Range
Initial
Value
Property*
V/
F
SL
Ref.
00
-
Jump Code
Jump
Code
1-99
20
O/A
O
I/P
p.71
01
0h1701
Built-in
communication
inverter ID
Int485 St
ID
1-250
1
O/A
O
I/P
p.275
02
52
0h1702
Built-in
communication
protocol
Int485
Proto
0
ModBus
RTU
0:
ModBus
RTU
O/A
O
I/P
p.275
2
LS Inv 485
03
52
0h1703
Built-in
communication
speed
Int485
BaudR
0
1200 bps
3:
9600
bps
O/A
O
I/P
p.275
1
2400 bps
2
4800 bps
3
9600 bps
4
19200 bps
5
38400 bps
6
56 Kbps
7
115 Kbps
53
04
52
0h1704
Built-in
communication
frame setting
Int485
Mode
0
D8/PN/S1
0:
D8/PN/
S1
O/A
O
I/P
p.275
1
D8/PN/S2
2
D8/PE/S1
3
D8/PO/S1
05
52
0h1705
Transmission
delay
after reception
Resp
Delay
0-1000(ms)
5ms
O/A
O
I/P
p.275
06
54
0h1706
Communication
option
S/W version
FBus S/W
Ver
-
0.00
O/A
O
I/P
-
07
54
0h1707
Communication
option
inverter ID
FBus ID
0-255
1
O/A
O
I/P
-
52
53
115,200bps
54
Displayed only when a communication option card is installed.