RS-485 Communication Features
Currently Registered CM Group Parameter
Status Parameter-1-
Status Parameter-8
Parameter communication code value registered at
CM.31-38 (Read-only)
Control Parameter-1-
Control Parameter-8
Parameter communication code value registered at
CM.51-58 (Read/Write access)
When registering control parameters, register the operation speed (0h0005, 0h0380, 0h0381)
and operation command (0h0006, 0h0382) parameters at the end of a parameter control frame.
For example, when the parameter control frame has 5 parameter control items (Para Control -
x), register the operation speed at Para Control-4 and the operation command to Para Control-5.
7.3 Communication Protocol
The built-in RS-485 communication supports LS INV 485 and Modbus-RTU protocols.
LS INV 485 Protocol
The slave device (inverter) responds to read and write requests from the master device
(PLC or PC).
Request
Normal Response
Error Response
• A request starts with ENQ and ends with EOT.
• A normal response starts with ACK and ends with EOT.