222
Learning Advanced Features
5.22 Read, Write, and Save Parameters
Use read, write and save function parameters on the inverter to copy parameters from the
inverter to the LCD loader or from the LCD loader to the inverter. The 7-Segment keypad
does not support this function.
Group
Code
Name
LCD Display
Parameter Setting
Setting
Range
Unit
CNF*
46
Parameter read
Parameter
Read
1
Yes
-
-
47
Parameter write
Parameter
Write
1
Yes
-
-
48
Parameter save
Parameter
Save
1
Yes
-
-
Read, Write, and Save Parameter Setting Details
Code
Description
CNF-46 Parameter
Read
Copies saved parameters from the inverter to the LCD loader. Saved
parameters on the LCD loader will be deleted and replaced with copied
parameters.
CNF-47 Parameter
Write
Copies saved parameters from the LCD loader to the inverter. Saved
parameters on the inverter will be deleted and replaced with copied
parameters. If an error occurs during parameter writing, previous saved
data will be used. If there is no saved data on the LCD loader, EEP
Rom Empty message will be displayed.
CNF-48 Parameter
Save
As parameters set during communication transmission are saved to
RAM, the setting values will be lost if the power goes off and on. When
setting parameters during communication transmission, select 1 (Yes)
from CNF-48 code to save the set parameter.