RS-485 Communication Features
276
Code
Description
CM.04 Int485 Mode
Set a communication configuration. Set the data length, parity check
method, and the number of stop bits.
Setting
Function
0
D8/PN/S1
8-bit data / no parity check / 1 stop bit
1
D8/PN/S2
8-bit data / no parity check / 2 stop bits
2
D8/PE/S1
8-bit data / even parity / 1 stop bit
3
D8/PO/S1
8-bit data / odd parity / 1 stop bit
CM.05 Resp Delay
Set the response time for the slave (inverter) to react to the request from
the master. Response time is used in a system where the slave device
response is too fast for the master device to process. Set this code to an
appropriate value for smooth master-slave communication.
Setting Operation Command and Frequency
To select the built-in RS485 communication as the source of command, set the Frq code to
6 (Int485) on the keypad (basic keypad with 7-segment display). On an LCD keypad, set
the DRV code to 3 (Int485). Then, set common area parameters for the operation
command and frequency via communication.
Group
Code
Name
LCD Display
Parameter
Setting
Setting range
Unit
Pr
12
Speed command loss
operation mode
Lost Cmd
Mode
1
Free-Run
0-5
-
13
Time to determine
speed command loss
Lost Cmd
Time
1.0
0.1-120
s
14
Operation frequency at
speed command loss
Lost Preset F
0.00
Start
frequency
Maximum
frequency
Hz
OU
31
Multi-function relay 1
Relay 1
13
Lost
0-35
-