394
Maintenance
Inspection
area
Inspection
item
Inspection
details
Inspection
method
Judgment
standard
Inspection
equipment
loose?
parts and
tighten all
screws.
Display
Display device
Is the display
value normal?
Check the
command
value on the
display
device.
Specified and
managed
values must
match.
Voltmeter,
Ammeter, etc.
Bi-annual Inspections
Inspection
area
Inspection
item
Inspection
details
Inspection
method
Judgment
standard
Inspection
equipment
Motor
Insulation
resistance
Megger test
(between the
input, output
and earth
terminals).
Disconnect
the cables for
terminals U/V/
W and test the
wiring.
Must be
above 5 MΩ
DC 500 V Megger
Do not run an insulation resistance test (Megger) on the control circuit as it may result in
damage to the product.