Only operates when Pr.08 (RST Restart) is set to 1(Yes). The number of
attempts to try the auto restart is set at Pr.09 (Auto Restart Count).
If a fault trip occurs during operation, the inverter automatically restarts
after the set time programmed at Pr.10 (Retry Delay). At each restart, the
inverter counts the number of tries and subtracts it from the number set at
Pr.09 until the retry number count reaches 0.
After an auto restart, if a fault trip does not occur within 60 sec, it will
increase the restart count number. The maximum count number is limited
by the number set at Pr.09 (Auto Restart Count).
If the inverter stops due to low voltage, emergency stop (Bx), inverter
overheating, or hardware diagnosis, an auto restart is not activated. At
auto restart, the acceleration options are identical to those of speed search
operation. Codes Cn.72–75 can be set based on the load. Information
about the speed search function can be found at 5.15 Speed Search
Operation on page 211.