Learning Advanced Features
Fault Trip Output using Multi-Function Output Terminal
and Relay
The inverter can output fault trip state using multi-function output terminal (Q1) and relay
(Relay 1).
Fault trip output on
delay
Fault trip output off
delay
* Available for 30-75kW models only.
Fault Trip Output by Multi-function Output Terminal and Relay - Setting Details
Fault trip relay operates based on the fault trip output settings.
When a fault trip occurs in the inverter, the relevant terminal and relay will
operate. Depending on the fault trip type, terminal and relay operation
can be configured as shown in the table below.
Operates when low voltage fault trips occur
Operates when fault trips other than low
voltage occur
Operates when auto restart fails (Pr. 08–09)
OU.32 Relay2
OU.33 Q1 Define
Select fault trip output terminal/relay and select 29(Trip Mode) at codes
OU. 31, 32, 33.
If a fault trip occurs, trip relay or multi-function output operates after the
time delay set in OU.53. Terminal is off with the input initialized after the
time delay set in OU.53.