216
Learning Advanced Features
[Example of auto restart with a setting of 2]
If the auto restart number is set, be careful when the inverter resets from a fault trip. The motor
may automatically start to rotate.
5.17 Operational Noise Settings (carrier frequency
settings)
Group
Code
Name
LCD Display
Parameter Setting
Setting
Range
Unit
Cn
04
Carrier
Frequency
Carrier Freq
3.0
1.015.0
kHz
05
Switching Mode
PWM* Mode
0
Normal
PWM
01
-
* PWM: Pulse width modulation
Operational Noise Setting Details
Code
Description
Cn.04 Carrier
Freq
Adjust motor operational noise by changing carrier frequency settings.
Power transistors (IGBT) in the inverter generate and supply high frequency
switching voltage to the motor. The switching speed in this process refers to
the carrier frequency. If the carrier frequency is set high, it reduces
operational noise from the motor, and if the carrier frequency is set low, it
increases operational noise from the motor.

Table of Contents

Other manuals for LSIS LSLV-S100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS LSLV-S100 and is the answer not in the manual?

LSIS LSLV-S100 Specifications

General IconGeneral
BrandLSIS
ModelLSLV-S100
CategoryController
LanguageEnglish

Related product manuals