Learning Advanced Features
exceeds the speed limit value.
Select a parameter from the Config (CNF) mode and then select21 Torque
Bias.
Select a multi-functional input terminal to set as the (35 Speed/Torque). If
you turn on the terminal while the operation is stopped, it operates in vector
control (speed limit) mode.
5.14 Energy Saving Operation
Manual Energy Saving Operation
If the inverter output current is lower than the current which is set at bA.14 (Noload Curr),
the output voltage must be reduced as low as the level set at Ad.51 (Energy Save). The
voltage before the energy saving operation starts will become the base value of the
percentage. Manual energy saving operation will not be carried out during acceleration and
deceleration.