144
Learning Basic Features
Frequency Jump
Use frequency jump to avoid mechanical resonance frequencies. Jump through frequency
bands when a motor accelerates and decelerates. Operation frequencies cannot be set
within the pre-set frequency jump band.
When a frequency setting is increased, while the frequency parameter setting value
(voltage, current, RS-485 communication, keypad setting, etc.) is within a jump frequency
band , the frequency will be maintained at the lower limit value of the frequency band. Then,
the frequency will increase when the frequency parameter setting exceeds the range of
frequencies used by the frequency jump band.
Group
Code
Name
LCD
Display
Parameter
Setting
Setting Range
Unit
Ad
27
Frequency jump
Jump Freq
0
No
01
-
28
Jump frequency
lower limit1
Jump Lo 1
10.00
0.00Jump frequency
upper limit 1
Hz
29
Jump frequency
upper limit1
Jump Hi 1
15.00
Jump frequency lower
limit 1Maximum
frequency
Hz
30
Jump frequency
lower limit 2
Jump Lo 2
20.00
0.00Jump frequency
upper limit 2
Hz
31
Jump frequency
upper limit 2
Jump Hi 2
25.00
Jump frequency lower
limit 2Maximum
frequency
Hz
32
Jump frequency
lower limit 3
Jump Lo 3
30.00
0.00Jump frequency
upper limit 3
Hz
33
Jump frequency
upper limit 3
Jump Hi 3
35.00
Jump frequency lower
limit 3Maximum
frequency
Hz

Table of Contents

Other manuals for LSIS LSLV-S100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS LSLV-S100 and is the answer not in the manual?

LSIS LSLV-S100 Specifications

General IconGeneral
BrandLSIS
ModelLSLV-S100
CategoryController
LanguageEnglish

Related product manuals