Learning Advanced Features
Automatic Energy Saving Operation
The amount of energy saving can be automatically calculated based on the rated motor
current (bA.13) and the no-load current (bA.14). From the calculations, the output voltage
can be adjusted.
If operation frequency is changed or acceleration and /deceleration is carried out by a stop
command during the energy saving operation, the actual Acc/Dec time may take longer than the
set Acc/Dec time due to the time required to return to the gerneral operation from the energy
saving operation.
5.15 Speed Search Operation
This operation is used to prevent fault trips that can occur while the inverter output voltage
is disconnected and the motor is idling. Because this feature estimates the motor rotation
speed based on the inverter output current, it does not give the exact speed.
PM speed search
pulse current
Speed search
operation selection
Speed search
reference current
Speed search
proportional gain
Speed search
integral gain
Output block time
before speed search
Multi-function relay 1
item
Multi-function output
1 item
*Displayed as on the Keypad.