Learning Advanced Features
219
5.19 Supply Power Transition
Supply power transition is used to switch the power source for the motor connected to the
inverter from the inverter output power to the main supply power source (commercial power
source), or vice versa.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
In
6571
Px terminal
configuration
Px Define(Px:
P1P7)
16
Exchange
-
-
OU
31
Multi-function relay1
items
Relay1
17
Inverter
Line
-
-
33
Multi-function output1
items
Q1 Define
18
Comm
Line
-
-
Supply Power Transition Setting Details
Code
Description
In.6571 Px Define
When the motor power source changes from inverter output to main
supply power, select a terminal to use and set the code value to 16
(Exchange). Power will be switched when the selected terminal is on. To
reverse the transition, switch off the terminal.