Maintenance
395
10.2 Replacing Major Components
Refer to following for information on replacing major components.
Exchange Cycle for Major Components
Following table shows the cycles and information for major components.
Components
Exchange standard
Symptom
Action
Cooling fan
3 years
Spinning failure
Make inquiries to the A/S center
and replace it with a new
product.
Main circuit electrolytic
condenser
3 years
Capacity
reduction
Make inquiries to the A/S center
and replace it with a new
product.
Main circuit relay
-
Operation
failure
Make inquiries to the A/S
center.
Note
The life times of major components are based on the operating rated load consecutively. The
lifetime may be different according to conditions and environment.
10.3 Storage and Disposal
Storage
If you are not using the product for an extended period, store it in the following way:
Store the product in the same environmental conditions as specified for operation (refer
to 1.3 Installation Considerations on page 8).
When storing the product for a period longer than 3 months, store it between 10˚C and
30˚C, to prevent depletion of the electrolytic capacitor.
Do not expose the inverter to snow, rain, fog, or dust.
Package the inverter in a way that prevents contact with moisture. Keep the moisture
level below 70% in the package by including a desiccant, such as silica gel.