EasyManua.ls Logo

LSIS LSLV-S100 - Page 295

LSIS LSLV-S100
469 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RS-485 Communication Features
281
An error response starts with NAK and ends with EOT.
A station ID indicates the inverter number and is displayed as a two-byte ASCII-HEX
string that uses characters 0-9 and A-F.
CMD: Uses uppercase characters (returns an IF error if lowercase characters are
encountered)please refer to the following table.
Character
ASCII-HEX
Command
‘R’
52h
Read
W’
57h
Write
X’
58h
Request monitor registration
Y;
59h
Perform monitor registration
Data: ASCII-HEX (for example, when the data value is 3000: 3000 0’’B’’B’’8h
30h 42h 42h 38h)
Error code: ASCII-HEX (refer to 7.3.1.4 Error Code on page 284)
Transmission/reception buffer size: Transmission=39 bytes, Reception=44 bytes
Monitor registration buffer: 8 Words
SUM: Checks communication errors via sum.
SUM=a total of the lower 8 bits values for station ID, command and data (Station
ID+CMD+Data) in ASCII-HEX.
For example, a command to read 1 address from address 3000:
SUM=‘0’+1’+’R’+‘3+‘0’+‘0’+0’+’1 = 30h+31h+52h+33h+30h+30h+30h+31h = 1A7h
(the control value is not included: ENQ, ACK, NAK, etc.).
ENQ
Station ID
CMD
Address
Number of
Addresses
SUM
EOT
05h
01
‘R’
3000’
1’
A7
04h
1 byte
2 bytes
1 byte
4 bytes
1 byte
2 bytes
1 byte
Note
Broadcasting
Broadcasting sends commands to all inverters connected to the network simultaneously. When
commands are sent from station ID 255, each inverter acts on the command regardless of the
station ID. However no response is issued for commands transmitted by broadcasting.

Table of Contents

Other manuals for LSIS LSLV-S100

Related product manuals