Page #351 background image
Table of Functions
337
Code
Comm.
Address
Name
LCD
Display
Setting Range
Initial
Value
Property*
V/
F
SL
Ref.
57
0h1639
Detected
frequency
FDT
Frequency
0.00-Maximum
frequency(Hz)
30.00
O/A
O
I/P
p.230
58
0h163A
Detected
frequency
band
FDT Band
0.00-Maximum
frequency(Hz)
10.00
O/A
O
I/P
p.240
61
0h163D
Pulse output
gain
TO Mode
0
Frequency
0:
Freque
ncy
O/A
O
I/P
p.237
1
Output Current
2
Output Voltage
3
DCLink
Voltage
4
Torque
5
Output Power
6
Idse
7
Iqse
8
Target Freq
9
Ramp Freq
10
Speed Fdb
12
PID Ref Value
13
PID Fdb Value
14
PID Output
15
Constant
62
0h163E
Pulse output
gain
TO Gain
-1000.0-1000.0(%)
100.0
O/A
O
I/P
p.237
63
0h163F
Pulse output
bias
TO Bias
-100.0-100.0(%)
0.0
O/A
O
I/P
p.237
64
0h1640
Pulse output
filter
TO Filter
0-10000(ms)
5
O/A
O
I/P
p.237
65
0h1641
Pulse output
constant
output 2
TO
Const %
0.0-100.0(%)
0.0
O/A
O
I/P
p.237
66
0h1642
Pulse output
monitor
TO
Monitor
0.0-1000.0(%)
0.0
O/A
O
I/P
p.237

Table of Contents

Other manuals for LSIS LSLV-S100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS LSLV-S100 and is the answer not in the manual?

LSIS LSLV-S100 Specifications

General IconGeneral
BrandLSIS
ModelLSLV-S100
CategoryController
LanguageEnglish

Related product manuals