Learning Advanced Features
239
Code
Description
and present output frequency is 30Hz, then the x-axis value on the next
graph is 50%.
OU.64 TO Filter
Sets filter time constant on analog output.
OU.65 TO
Const %
If analog output item is set to constant, the analog pulse output is dependent
on the set parameter values.
OU.66 TO
Monitor
Monitors analog output value. Displays the maximum output pulse (32kHz)
as a percentage (%) of the standard.
Note
OU.08 AO2 Gain and OU.09 AO2 Bias Tuning Mode on 420mA output
1 Set OU.07 (AO2 Mode) to constant, and set OU.11 (AO2 Const %) to 0.0 %.
2 Set OU.09 (AO2 Bias) to 20.0% and then check current output. 4mA output should be
displayed.
3 If the value is less than 4mA, gradually increase OU.09 (AO2 Bias) until 4mA is measured.
If the value is more than 4mA, gradually decrease OU.09 (AO2 Bias) until 4mA is
measured.
4 Set OU.11 AO2 Const % to 100.0%
Set OU.08 (AO2 Gain) to 80.0% and measure current output at 20mA. If the value is less
than 20mA, gradually increase OU.08 (AO2 Gain) until 20mA is measured. If the value is
more than 20mA, gradually decrease OU.08 (AO2 Gain) until 20mA is measured.
The functions for each code are identical to the descriptions for the 010V voltage outputs with
an output range 420mA.