TI Pulse Input Setting Details
In case of Standard I/O (excluding 30-75kW models), Pulse input TI and
Multi-function terminal P5 share the same therminal.
Set the In.69 P5 Define to 54(TI).
Configures the frequency reference at the maximum pulse input. The
frequency reference is based on 100% of the value set with In.96.
• If In.01 is set to 40.00 and codes In.93–96 are set at default, 32kHz
input to TI yields a frequency reference of 40.00Hz.
• If In.96 is set to 50.00 and codes In.01, In.93–95 are set at default,
32kHz input to the TI terminal yields a frequency reference of 30.00Hz.
Displays the pulse frequency supplied at TI.
Sets the time for the pulse input at TI to reach 63% of its nominal frequency
(when the pulse frequency is supplied in multiple steps).
In.93 TI Pls x1–
In.96 TI Perc y2
Configures the gradient level and offset values for the output frequency.
In.97 TI Inverting–
In.98 TI
Quantizing
Identical to In.16–17 (refer to In.16 V1 Inverting/In.17.V1 Quantizing on page
105).