109
Learning Basic Features
4.1.3.3 Setting a Reference Frequency using Input Current (I2)
You can set and modify a frequency reference using input current at the I2 terminal after
selecting current input at SW 2. Set the Frq (Frequency reference source) code in the
Operation group to 5 (I2) and apply 420mA input current to I2.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
Operation
Frq
Frequency reference
source
Freq Ref Src
5
I2
012
-
In
01
Frequency at
maximum analog
input
Freq at
100%
60.00
0 Maximum
Frequency
Hz
50
I2 input monitor
I2 Monitor
0.00
0.0024.00
mA
52
I2 input filter time
constant
I2 Filter
10
010000
ms
53
I2 minimum input
current
I2 Curr x1
4.00
0.0020.00
mA
54
I2 output at minimum
current (%)
I2 Perc y1
0.00
0100
%
55
I2 maximum input
current
I2 Curr x2
20.00
0.0024.00
mA
56
I2 output at maximum
current (%)
I2 Perc y2
100.00
0.00100.00
%
61
I2 rotation direction
options
I2 Inverting
0
No
01
-
62
I2 Quantizing level
I2
Quantizing
0.04
0*, 0.04
10.00
%
* Quantizing is disabled if 0 is selected.
Input Current (I2) Setting Details
Code
Description
In.01 Freq at
100%
Configures the frequency reference for operation at the maximum current
(when In.56 is set to 100%).
If In.01 is set to 40.00Hz, and default settings are used for In.5356,
20mA input current (max) to I2 will produce a frequency reference of
40.00Hz.
If In.56 is set to 50.00 (%), and default settings are used for In.01
(60Hz) and In.5355, 20mA input current (max) to I2 will produce a
frequency reference of 30.00Hz (50% of 60Hz).
In.50 I2 Monitor
Used to monitor input current at I2.
In.52 I2 Filter
Configures the time for the operation frequency to reach 63% of target
frequency based on the input current at I2.