Learning Advanced Features
241
Code
Description
2
FDT-2
Outputs a signal when the user set frequency and
detected frequency (FDT Frequency) are equal,
and fulfills FDT-1 condition at the same time.
[Absolute value (set frequency-detected frequency)
< detected frequency width/2]&[FDT-1]
Detected frequency width is 10Hz. When the
detected frequency is set to 30Hz, FDT-2 output is
as shown in the graph below.
3
FDT-3
Outputs a signal when the Absolute value (output
frequencyoperation frequency) < detected
frequency width/2.
Detected frequency width is 10Hz. When detected
frequency is set to 30Hz, FDT-3 output is as shown
in the graph below.
4
FDT-4
Output signal can be separately set for acceleration
and deceleration conditions.
In acceleration: Operation frequency
Detected frequency