184
Learning Advanced Features
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
24
Rotor time
constant
Tr
145
25-5000
ms
Default Motor Parameter Settings
Motor Capacity
(kW)
Rated
Current (A)
No-load
Current (A)
Rated Slip
Frequency(Hz)
Stator
Resistance(
)
Leakage
Inductance (mH)
200V
0.2
1.1
0.8
3.33
14.0
40.4
0.4
2.4
1.4
3.33
6.70
26.9
0.75
3.4
1.7
3.00
2.600
17.94
1.5
6.4
2.6
2.67
1.170
9.29
2.2
8.6
3.3
2.33
0.840
6.63
3.7
13.8
5.0
2.33
0.500
4.48
5.5
21.0
7.1
1.50
0.314
3.19
7.5
28.2
9.3
1.33
0.169
2.844
11
40.0
12.4
1.00
0.120
1.488
15
53.6
15.5
1.00
0.084
1.118
18.5
65.6
19.0
1.00
0.068
0.819
22
76.8
21.5
1.00
0.056
0.948
400V
0.2
0.7
0.5
3.33
28.00
121.2
0.4
1.4
0.8
3.33
14.0
80.8
0.75
2.0
1.0
3.00
7.81
53.9
1.5
3.7
1.5
2.67
3.52
27.9
2.2
5.0
1.9
2.33
2.520
19.95
3.7
8.0
2.9
2.33
1.500
13.45
5.5
12.1
4.1
1.50
0.940
9.62
7.5
16.3
5.4
1.33
0.520
8.53
11
23.2
7.2
1.00
0.360
4.48
15
31.0
9.0
1.00
0.250
3.38
18.5
38.0
11.0
1.00
0.168
2.457
22
44.5
12.5
1.00
0.168
2.844