Preparing the Installation
14
Ground Cable and Power Cable Specifications (30-75kW)
Load (kW)
Ground
Power I/O
mm
2
AWG
mm
2
AWG
R/S/T
U/V/W
R/S/T
U/V/W
3Phase
400V
30
16
5
25
25
4
4
37
45
70
70
1/0
1/0
55
35
3
75
2
Signal (Control) Cable Specifications
Terminals
Signal Cable
Without Crimp Terminal
Connectors
(Bare wire)
With Crimp Terminal Connectors
(Bootlace Ferrule)
mm
2
AWG
mm
2
AWG
P1~P7*/CM/VR/V1/I2
/AO1,AO2/Q1/EG/24/TI/
TO* /SA,SB,SC/S+,
S-,SG
0.75
18
0.5
20
A1/B1/C1/A2/C2
1.0
17
1.5
15
* Standard I/O doesnt support P6/P7/TI/TO terminal. Refer to Step 4 Control Terminal