EasyManua.ls Logo

LSIS LSLV-S100 - Page 307

LSIS LSLV-S100
469 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RS-485 Communication Features
293
Comm.
Address
Parameter
Scale
Unit
Assigned content by bit
B4
5: Decelerating to stop
6: H/W OCS
7: S/W OCS
8: Dwell operating
B3
0: Stopped
1: Operating in forward direction
2: Operating in reverse direction
3: DC operating (0 speed control)
B2
B1
B0
0h0306
Inverter operation
frequency
command source
-
-
B15
Operation command source
0: Keypad
1: Communication option
2: User Sequence
3: Built-in RS 485
4: Terminal block
B14
B13
B12
B11
B10
B9
B8
B7
Frequency command source
0: Keypad speed
1: Keypad torque
2-4: Up/Down operation speed
5: V1, 7: V2, 8: I2
9: Pulse
10: Built-in RS 485
11: Communication option
12: User Sequence
13: Jog
14: PID
25-39: Multi-step speed
frequency
B6
B5
B4
B3
B2
B1
B0
0h0307
LCD keypad S/W
version
-
-
(Ex.) 0h0100: Version 1.00
0h0308
LCD keypad title
version
-
-
(Ex.) 0h0101: Version 1.01
0h0309 -0h30F
Reserved
-
-
-
0h0310
Output current
0.1
A
-
0h0311
Output frequency
0.01
Hz
-
0h0312
Output rpm
0
rpm
-
0h0313
Motor feedback
speed
0
rpm
-32768 rpm-32767 rpm (directional)
0h0314
Output voltage
1
V
-
0h0315
DC Link voltage
1
V
-
0h0316
Output power
0.1
kW
-
0h0317
Output torque
0.1
%
-

Table of Contents