RS-485 Communication Features
295
Comm.
Address
Parameter
Scale
Unit
Assigned content by bit
0h0325
Reserved
0.01
%
0h0326
AI3
0.01
%
Analog input V2 (I/O board)
0h0327
AI4
0.01
%
Analog input I2 (I/O board)
0h0328
AO1
0.01
%
Analog output 1 (I/O board)
0h0329
AO2
0.01
%
Analog output 2 (I/O board)
0h032A
AO3
0.01
%
Analog output 3 (Extension I/O)
0h032B
AO4
0.01
%
Reserved
0h032C
Reserved
-
-
-
0h032D
Inverter module
temperature
1
-
0h032E
Inverter power
consumption
1
kWh
-
0h032F
Inverter power
consumption
1
MW
h
-
0h0330
Latch type trip
information - 1
-
-
BI5
Fuse Open Trip
BI4
Over Heat Trip
BI3
Arm Short
BI2
External Trip
BI1
Overvoltage Trip
BI0
Overcurrent Trip
B9
NTC Trip
B8
Reserved
B7
Reserved
B6
Input open-phase trip
B5
Output open-phase trip
B4
Ground Fault Trip
B3
E-Thermal Trip
B2
Inverter Overload Trip
B1
Underload Trip
B0
Overload Trip
0h0331
Latch type trip
information - 2
-
-
BI5
Reserved
BI4
Reserved
BI3
Safety B
BI2
Safety A
BI1
Reserved
BI0
Bad option card
B9
No motor trip
B8
External brake trip
B7
Bad contact at basic I/O
board
B6
Pre PID Fail
B5
Error while writing parameter
B4
Reserved
B3
FAN Trip