EasyManua.ls Logo

LSIS LSLV-S100 - Page 357

LSIS LSLV-S100
469 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table of Functions
343
Cod
e
Comm.
Address
Name
LCD Display
Setting Range
Initial
Value
Property*
V/
F
SL
Ref.
17
60
0h1811
PID reference
monitor
PID Ref
Value
(%)
50.00
-/A
O
I/P
p.176
18
60
0h1812
PID feedback
monitor
PID Fdb
Value
(%)
0.00
-/A
O
I/P
p.176
19
60
0h1813
PID reference
setting
PID Ref Set
-100.00-
100.00(%)
50.00
O/A
O
I/P
p.176
20
60
0h1814
PID reference
source
PID
Ref Source
0
Keypad
0:
Keypa
d
X/A
O
I/P
p.176
1
V1
3
V2
4
I2
5
Int 485
7
FieldBus
8
UserSe
qLink
11
Pulse
21
60
0h1815
PID feedback
source
PID
F/B Source
0
V1
0:V1
X/A
O
I/P
p.176
2
V2
3
I2
4
Int 485
6
FieldBus
7
UserSe
qLink
10
Pulse
22
60
0h1816
PID controller
proportional
gain
PID P-Gain
0.0-1000.0(%)
50.0
O/A
O
I/P
p.176
23
60
0h1817
PID controller
integral time
PID I-Time
0.0-200.0(s)
10.0
O/A
O
I/P
p.176
24
60
0h1818
PID controller
differentiation
time
PID D-Time
0-1000(ms)
0
O/A
O
I/P
p.176
25
60
0h1819
PID controller
feed-forward
compensation
gain
PID F-Gain
0.0-1000.0(%)
0.0
O/A
O
I/P
p.176
26
60
0h181A
Proportional
gain scale
P Gain Scale
0.0-100.0(%)
100.0
X/A
O
I/P
p.176
27
60
0h181B
PID output
filter
PID Out LPF
0-10000(ms)
0
O/A
O
I/P
p.176
28
60
0h181C
PID Mode
PID Mode
0
Process
PID
0
X/A
O
I/P
-
1
Normal
PID

Table of Contents