85
Learning to Perform Basic Operations
3.3.4.2 30-75kW Models
The following example demonstrates how to revert all the parameter settings back to the
factory default (Parameter Initialization). Parameter initialization may be performed for
separate groups in Parameter mode as well.
Monitor mode is displayed.
Press the [MODE] key to move to the Config (CNF)
mode.
Press the [] key to go to CNF-40 (Parameter Init).
Press the [PROG/ENT] key.
In the list of options, select All Groups, and then press
the [PROG/ENT] key.
The parameter initialization option is displayed again
when the initialization is complete.