109
"B" Group: Fine Tuning Functions Section 3-6
low speed, the inverter may output a frequency that instructs the motor to
rotate in the direction opposite to that specified by the operation command.
3-6-9 Reduced voltage start
The reduced voltage start function enables you to make the inverter increase
the output voltage gradually when starting the motor.
Set a small value for the reduced voltage start selection (b036) if you intend to
increase the start torque. On the other hand, setting a small value will cause
the inverter to perform full-voltage starting and to easily trip because of over-
current.
"B" Function Run
Mode
Edit
Defaults
Func.
Code
Name Description EU Units
B035 Rotation direction restriction Three option codes:
00 No restriction
01 Reverse rotation is restricted
02 Forward rotation is restricted
8 00
b046 Reverse run protection Two option codes:
00 No protection
01 Reverse rotation is protected
8 00
"B" Function Run
Mode
Edit
Defaults
Func.
Code
Name Description EU Units
b036 Reduced voltage start
selection
Set range, 00 (disabling the func-
tion), 01 (approx. 6ms) to 255
(approx. 1.5s)
8 02
FW
Start freq. b082
Output freq.
Reduced voltage start
b036
Output voltage
00 0601