EasyManua.ls Logo

Omron MX2 - Write in Holding Register [06 H]

Omron MX2
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
271
Network Protocol Reference Section B-3
Write in Holding Register [06h]:
This function writes data in a specified holding register. An example follows:
Write "50 Hz" as the first Multi-speed 0 (A020) in an inverter having slave
address "5."
This example uses change data "500 (1F4h)" to set "50 Hz" as the data
resolution of the register "1029h" holding the first Multi-speed 0 (A020) is
0.1 Hz
Note 1 No response is made for a broadcasting query.
Note 2 The PDU Register Number are addressed starting at zero. Therefore register
numbered "1029h" are addressed as "1028h". Register address value (trans-
mitted on Modbus line) is 1 less than the Register Number.
When writing in a selected holding register fails, see the exception response.
Query: Response:
No. Field Name Example
(Hex)
No. Field Name Example
(Hex)
1 Slave address *1 08 1 Slave address 08
2 Function code 06 2 Function code 06
3 Register start
address *2
(high order)
10 3 Register start
address *2 (high
order)
10
4 Register start
address *2
(low order)
28 4 Register start
address *2
(low order)
28
5 Change data
(high order)
01 5 Change data
(high order)
01
6 Change data
(low order)
F4 6 Change data
(low order)
F4
7 CRC-16 (high order) 0D 7 CRC-16 (high order) 0D
8 CRC-16 (low order) 8C 8 CRC-16 (low order) 8C

Table of Contents

Other manuals for Omron MX2

Related product manuals