315
Parameter Settings for Keypad Entry Section C-2
C-2-3 Fine Tuning Functions
"B" Group Parameters Default Setting B031=10 User
Setting
Func.
Code
Name (EU)
B001 Restart mode on power failure /
under-voltage trip
00 ✓
B002 Allowable under-voltage power fail-
ure time
1.0 ✓
B003 Retry wait time before motor restart 1.0 ✓
B004 Instantaneous power failure / under-
voltage trip alarm enable
00 ✓
B005 Number of restarts on power failure /
under-voltage trip events
00 ✓
B007 Restart frequency threshold 0.00 ✓
B008 Restart mode on over voltage / over
current
00 ✓
B010 Number of retry on over voltage /
over current
3 ✓
B011 Retry wait time on over voltage /
over current
1.0 ✓
B012
B212
Level of electronic thermal
Level of electronic thermal,
2nd motor
Rated current for
each inverter
Rated current for
each inverter
✓
✓
B013 Electronic thermal characteristic 01 ✓
B213 Electronic thermal characteristic,
2nd motor
01 ✓
B015 Free setting, electronic thermal
frequency (1)
0. ✓
B016 Free setting, electronic thermal
current (1)
0.0 ✓
B017 Free setting, electronic thermal
frequency (2)
0. ✓
B018 Free setting, electronic thermal
current (2)
0.0 ✓
B019 Free setting, electronic thermal
frequency (3)
0. ✓
B020 Free setting, electronic thermal
current (3)
0.0 ✓
B021 Overload restriction operation mode 01 ✓
B221 Overload restriction operation mode,
2nd motor
01 ✓
B022
B222
Overload restriction level
Overload restriction level, 2nd motor
Rated current x
1.5 (HD)
1.2 (ND)
Rated current x
1.5 (HD)
1.2 (ND)
✓
✓
B023
B223
Deceleration rate at overload
restriction
Deceleration rate at overload
restriction, 2nd motor
1.0
1.0
✓
✓
B024 Overload restriction operation
mode 2
01 ✓
B025 Overload restriction level 2 Rated current x
1.5 (HD)
1.2 (ND)
✓
B026 Deceleration rate 2 at overload
restriction
1.0 ✓