168
Connecting to PLCs and Other Devices Section 4-2
4-2-1 Example Wiring Diagram
The schematic diagram below provides a general example of logic connector
wiring, in addition to basic power and motor wiring converted in Chapter 2.
The goal of this chapter is to help you determine the proper connections for
the various terminals shown below for your application needs.
Breaker, MCCB
or GFI
Power source,
3-phase or
1-phase, per
inverter model
Input
circuits
24V
P24
+ -
1
2
3/GS1
4/GS2
5/PTC
Forward
Thermistor
Intelligent inputs,
7 terminals
GND for logic inputs
NOTE:
For the wiring of intelligent
I/O and analog inputs,
be sure to use twisted
pair / shielded cable.
Attach the shielded wire
for each signal to its
respective common
terminal at the inverter
end only.
Input impedance of
each intelligent input is
4.7 kΩ
[5] configurable as
discrete input or
thermistor input
AM
Volt. Meter
H
L
0~10VDC
4~20mA
GND for analog signals
MX2
Motor
PD/+1
P/+
R