176
Using Intelligent Input Terminals Section 4-5
The two diagrams below input wiring circuits using the inverter's internal
+24 V supply. Each diagram shows the connection for simple switches, or for
a field device with transistor outputs. Note that in the lower diagram, it is nec-
essary to connect terminal [L] only when using the field device with transis-
tors. Be sure to use the correct connection of the short bar shown for each
wiring diagram.
Sinking Inputs, Internal Supply
Short bar = [PLC] – [P24] position
GND
7
1
Field device
Open collector outputs,
NPN transistors
MX2
P24
1
7
24 V
PLC
Input
circuits
+
-
Logic GND
Input common
Short bar
Input switches
L
Sourcing Inputs, Internal Supply
Short bar = [PLC] – [L] position
Common to
[P24]
7
1
Field device
PNP transistor
sousing outputs
MX2
P24
1
7
24 V
PLC
Input
circuits
+
-
Logic GND
Input common
Short bar
Input switches
L
GND
to PNP bias
circuits

Table of Contents

Other manuals for Omron MX2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 and is the answer not in the manual?

Omron MX2 Specifications

General IconGeneral
ModelMX2
CategoryInverter
Enclosure RatingIP20
Control MethodV/f control, Sensorless vector control
Frequency Range0.1 to 400 Hz
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheat, Short circuit
CommunicationModbus RTU
Ambient Temperature-10 to 50 °C (without freezing or condensation)
Overload Capacity150% for 60 seconds
Cooling MethodFan Cooled
Humidity5 to 95% RH (without condensation)
AltitudeUp to 1000m without derating
Voltage200-240 VAC, 380-480 VAC
Braking UnitBuilt-in (for certain models), Optional External

Related product manuals