EasyManuals Logo

Omron MX2 User Manual

Omron MX2
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #229 background imageLoading...
Page #229 background image
207
Using Intelligent Output Terminals Section 4-6
The alarm relay output can be configured in two main ways:
Trip/Power Loss Alarm - The alarm relay is configured as normally closed
(
C036=01) by default, shown below (left). An external alarm circuit that
detects broken wiring also as an alarm connects to [AL0] and [AL1]. After
powerup and short delay (< 2 seconds), the relay energizes and the alarm
circuit is OFF. Then, either an inverter trip event or an inverter power loss
will de-energize the relay and open the alarm circuit
Trip Alarm - Alternatively, you can configure the relay as normally open
(
C036=00), shown below (right). An external alarm circuit that detects bro-
ken wiring also as an alarm connects to [AL0] and [AL2]. After powerup,
the relay energizes only when an inverter trip event occurs, opening the
alarm circuit. However, in this configuration, an inverter power loss does
not open the alarm circuit.
Be sure to use the relay configuration that is appropriate for your system
design. Note that the external circuits shown assume that a closed circuit = no
alarm condition (so that a broken wire also causes an alarm). However, some
systems may require a closed circuit = alarm condition. In that case, then use
the opposite terminal [AL1] or [AL2] from the ones shown.
N.C. contacts (C036=01) N.O. contacts (C036=00)
During normal
operation
When an alarm occurs
or when power is OFF
During normal operation
or when power is OFF
When an alarm occurs
AL1
Power
supply
Load
AL0 AL2
AL1
Load
AL0 AL2
Power
supply
AL1
Load
AL0 AL2
Power
supply
AL1
Load
AL0 AL2
Power
supply
Power Run Mode AL0-AL1 AL0-AL2
ON Normal Closed Open
ON Trip Open Closed
OFF Open Closed
Power Run Mode AL0-AL1 AL0-AL2
ON Normal Open Closed
ON Trip Closed Open
OFF Open Closed

Table of Contents

Other manuals for Omron MX2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 and is the answer not in the manual?

Omron MX2 Specifications

General IconGeneral
ModelMX2
CategoryInverter
Enclosure RatingIP20
Control MethodV/f control, Sensorless vector control
Frequency Range0.1 to 400 Hz
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheat, Short circuit
CommunicationModbus RTU
Ambient Temperature-10 to 50 °C (without freezing or condensation)
Overload Capacity150% for 60 seconds
Cooling MethodFan Cooled
Humidity5 to 95% RH (without condensation)
AltitudeUp to 1000m without derating
Voltage200-240 VAC, 380-480 VAC
Braking UnitBuilt-in (for certain models), Optional External

Related product manuals