10.10 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 549
Setting Function Description Ref.
1E Reference Sample
Hold
Sets the command to sample the frequency reference at terminals A1, A2, or A3 and hold
the frequency reference at that frequency.
875
20 to 2F External Fault
Sets a command to stop the drive when a failure or fault occurs on an external device.
20 : External Fault (NO-Always-Ramp)
21 : External Fault (NC-Always-Ramp)
22 : External Fault (NO-@Run-Ramp)
23 : External Fault (NC-@Run-Ramp)
24 : External Fault (NO-Always-Coast)
25 : External Fault (NC-Always-Coast)
26 : External Fault (NO-@Run-Coast)
27 : External Fault (NC-@Run-Coast)
28 : External Fault (NO-Always-FStop)
29 : External Fault (NC-Always-FStop)
2A : External Fault (NO-@Run-FStop)
2B : External Fault (NC-@Run-FStop)
2C : External Fault (NO-Always-Alarm)
2D : External Fault (NC-Always-Alarm)
2E : External Fault (NO-@Run-Alarm)
2F : External Fault (NC-@Run-Alarm)
876
30 PID Integrator
Reset
Sets the command to reset and hold the PID control integral to 0 when the terminal is
ON.
877
31 PID Integrator
Hold
Sets the command to hold the integral value of the PID control while the terminal is
activated.
877
32 Multi-Step Speed
Reference 4
Sets the command to switch d1-09 to d1-16 [Reference 9 to 16] with multi-step speed
references 1, 2 and 3.
877
34 PID Soft Starter
Disable
Sets the PID soft starter function.
ON : Disabled
OFF : Enabled
877
35 PID Input (Error)
Invert
Sets the command to turn the terminal ON and OFF to switch the PID input level
(polarity).
877
3E PID Setpoint
Selection 1
Set this function and H1-xx = 3F [PID Setpoint Selection 2] together. Sets the function to
switch the PID setpoint to b5-58 to b5-60 [PID Setpoint 2 to 4].
878
3F PID Setpoint
Selection 2
Set this function and H1-xx = 3E [PID Setpoint Selection 1] together. Sets the function to
switch the PID setpoint to b5-58 to b5-60 [PID Setpoint 2 to 4].
878
40 Forward RUN (2-
Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 41
[Reverse Run Command (2-Wire Seq)] together.
ON : Forward Run
OFF : Run Stop
Note:
• Turning ON the Forward Run command terminal and the Reverse Run command
terminal will cause alarm EF [FWD/REV Run Command Input Error] and the motor
will ramp to stop.
• Initialize the drive with a 2-wire sequence to set the Forward Run command to
terminal S1.
• This function will not operate at the same time as H1-xx = 42, 43 [Run Command/
FWD/REV Command (2-Wire Seq 2)].
878