System 3505 Installation & Operation Manual
Digitize, Inc. 700248-0002 Rev. C 02/16
Specification Subject to Change Without Notice
8-5
The SST SLOW relay will code out the same box number as the Q-IR or Q-I/O device.
Pressing the STOP key will abort both the SST SLOW and the SST to the Q-Mux
device. To transmit only via the SST SLOW (or FAST), use the @B command in
place of the @Q command. Multiple transmissions are made by adding several @B or
@Q (or any other supported @ commands) to the text screens. Only one box
transmission will be made at any one time.
For example, Zone 2 Alarm display reads:
Joe’s Hardware 1st Floor
@Q2-01-1234
This translates to: Node #2, Relay #01 will code 4 rounds for Box 1234.
8.4.2
Relay Control
The @R command capability requires the purchase and installation of the Relay
Control option P/N 000001-0032) and the Q-1R module.
The @R command may be entered any place on the nine pages specific user text
messages. A relay command format for the Q-Mux would be:
@R9001-14
This translates to: Q-Mux Node #9001 Relay #14 (ON for Alarm, OFF for Secure
or Trouble).
End of Chapter