EasyManua.ls Logo

DIGITIZE SYSTEM 3505 - Trouble Reminder; Applicable Publications

DIGITIZE SYSTEM 3505
175 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System 3505 Installation & Operation Manual
Digitize, Inc. 700248-0002 Rev. C 02/16
Specification Subject to Change Without Notice
1-8
1.10 TROUBLE REMINDER
Per NFPA guidelines, the SYSTEM 3505 must alert the operator any time that a Trouble
condition remains continuously active for longer then 24 hours. Each time a Trouble
condition remains active for longer then 24 hours, the SYSTEM 3505 will print to the
logging printer the current date and time along with the words "TROUBLE REMINDER" (in
reverse video text). The account type, i.e. Zone, Dlr, Sys, etc. as well as the account number
will also be printed. The Trouble indicator will begin to flash, and the trouble sound will be
activated at this time. The operator must ACK this reminder condition.
The user can select the time of the day that this 24 hour reminder will print. NOTE: because
every trouble and O/S condition will be printed at this 24 hour time interval, the first
indication of an account’s trouble will be less that 24 hours then every 24 hours thereafter.
1.11 APPLICABLE PUBLICATIONS
FCC “Rules and Regulations”, Part 15
National Electric Code
NFPA 72 (Proprietary) INSTALLATION
End of Chapter

Table of Contents

Other manuals for DIGITIZE SYSTEM 3505

Related product manuals