Preliminary steps
"Locating the defective server" on page
47.
Check which PSU is defective.
PSU is defective when the PSU status indicator lights orange. For more
information, see "Indicator on hot-plug PSU" on page 553.
Only when replacing a PSU in a non-redundant configuration: "Shutting
down the server" on page 50.
Remove the power cord from the defective PSU, see "Disconnecting the
power cord" on page 50.
Removing the defective hot-plug PSU
Remove the PSU, see "Removing a hot-plug PSU" on page 129.
Installing the new hot-plug PSU
Install the PSU, see "Installing a hot-plug PSU" on page 126.
Concluding steps
"Connecting the power cord" on page 65.
Only when replacing a PSU in a non-redundant configuration: "Switching on
the server" on page 71.
"Performing a fan test" on page 117.
A fan test does not need to be performed if the hot-plug PSU is
actively replaced. iRMC runs automatically
.
Check that the PSU status indicator is lit green.
Power supply unit (PSU)
134 Upgrade and Maintenance Manual RX2540 M7