EasyManua.ls Logo

Honeywell Gamewell-FCI E3 Series - 3.3.1 Intelligent Loop Interface XP95 - Main Board (ILI95-MB-E3) Wiring Connections

Honeywell Gamewell-FCI E3 Series
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E3 Series Installation/Operation Manual P/N 9000-0574:I 11/04/10 103
Intelligent Loop Interface XP95-Main Board Connections E3 Series System Connections
3.3.1 Intelligent Loop Interface XP95 - Main Board (ILI95-MB-E3)
Wiring Connections
Field wiring connections for the ILI95-MB-E3 is shown in Table 3.3.1.1. All wiring is Power-
limited except the local energy City Box that is non power-limited.
Designation Description Comments
TB1-1, TB1-3 +24 V IN +24 VDC Input from PM-9/PM-9G TB4-1
TB1-2, TB1-4 GND Common negative from PM-9/PM-9G TB4-2
TB2-1 NAC1 B+ Notification Appliance Circuit 1 (See Note 6)
TB2-2 NAC1 B - Notification Appliance Circuit 1 (See Note 6)
TB2-3 NAC 1 A+ Notification Appliance Circuit 1 (See Note 6)
TB2-4 NAC 1 A- Notification Appliance Circuit 1 (See Note 6)
TB2-5 NAC 2 B+ Notification Appliance Circuit 2 (See Note 6)
TB2-6 NAC 2 B- Notification Appliance Circuit 2 (See Note 6)
TB2-7 NAC 2 A+ Notification Appliance Circuit 2 (See Note 6)
TB2-8 NAC 2 A- Notification Appliance Circuit 2 (See Note 6)
TB3-1 AUX RS485 A Output to LCD-E3, ASM-16, ANU-48, LCD-7100, DACT-E3 (See Note 3)
TB3-2 AUX RS485 B Output to LCD-E3, ASM-16, ANU-48, LCD-7100, DACT-E3 (See Note 3)
TB3-3 Earth Ground Connect to water pipe ground
TB3-4 Resettable B+ Auxiliary resettable 24 VDC power
TB3-5 GND Common negative
TB3-6 Non-resettable B+ Auxiliary non-resettable 24 VDC power
TB3-7 GND Common negative
TB3-8 Municipal Ckt+ Output to Local Energy City Box or Remote Station or Releasing Solenoid -
Non Power-Limited
TB3-9 Municipal Ckt - Output to Local Energy City Box or Remote Station or Releasing Solenoid -
Non Power-Limited
TB4-1 SLC 2 A- SLC 2 Style 6 / 7 Return (See Note 5)
TB4-2 SLC 2 A+ SLC 2 Style 6 / 7 Return (See Note 5)
TB4-3 SLC 2 B- SLC 2 Style 4 / 6 / 7 Out (See Note 5)
TB4-4 SLC 2 B+ SLC 2 Style 4 / 6 / 7 Out (See Note 5)
TB5-1 Alarm DC NC Alarm relay contact, N/C
TB5-2 Alarm DC NO Alarm relay contact, N/O
TB5-3 Alarm DC Common Alarm relay contact, Common
TB5-4 Supv DC NC Supervisory relay contact, N/C
TB5-5 Supv DC NO Supervisory relay contact, N/O
TB5-6 Supv DC Common Supvervisory relay contact, Common
TB5-7 Trbl DC NC Trouble relay contact, N/C
TB5-8 Trbl DC NO Trouble relay contact, N/O
TB5-9 Trbl DC Common Trouble relay contact, Common
TB6-1 RS232 GND To red lead on download cable P/N 75267
TB6-2 RS232 RxD To black lead on download cable P/N 75267 RS-232 Download
or Printer Port
TB6-3 Supervision Optional Printer Supervision
TB6-4 RS232 TxD To green lead on download cable P/N 75267
TB7-1 SLC 1 A- SLC 1 Style 6 / 7 Return (See Note 5)
TB7-2 SLC 1 A+ SLC 1 Style 6 / 7 Return (See Note 5)
TB7-3 SLC 1 B- SLC 1 Style 4 / 6 / 7 Out (See Note 5)
TB7-4 SLC 1 B+ SLC 1 Style 4 / 6 / 7 Out / (See Note 5)
W1, W2, W3 Factory Jumpers Factory use only. (Default OUT)
Table 3.3.1.1 ILI95-MB-E3 Field Wiring Connections