10 E3 Series Installation/Operation Manual P/N 9000-0574:I 11/04/10
Section 1: System Overview
1.1 Description
The Gamewell-FCI E3 Series
®
Expandable Emergency Evacuation System is a multiprocessor
based analog/addressable fire alarm control panel, designed for commercial, industrial and
institutional fire alarm applications. The E3 Series
®
is Listed by Underwriters Laboratories under
Standard UL 864, 9th Edition. It is suitable for the following signaling services:
Automatic Fire Detector Alarm
Manual Fire Alarm
Waterflow Alarm
Supervisory
Automatic Smoke Alarm, non-coded and master coded operation
Releasing Device Service
When the System is configured and installed under the supervision of a Gamewell-FCI factory
trained and certified distributor, the E3 Series complies with the requirements of the following
National Fire Protection Association (NFPA) Standards:
NFPA 13 Installation of Sprinkler Systems
NFPA 16 Deluge Foam - Water Sprinkler Systems
NFPA 72 National Fire Alarm Code:
Central Station Fire Alarm Systems
Local Fire Alarm Systems
Auxiliary Fire Alarm Systems
Remote Station Fire Alarm Systems
Proprietary Fire Alarm Systems
1.2 Standard Features
Two (2), Class A, Style 6, 7* or Class B, Style 4 Signaling Line Circuits
Two (2), Class A, Style Z or Class B, Style Y Notification Appliance Circuits, 2.0 amp each
Alarm, Trouble and Supervisory dry contacts
Accommodates 159 Gamewell-FCI Approved, UL
®
Listed compatible analog sensors per
signaling line circuit (ILI-MB-E3 or ILI-S-E3 only).
Accommodates 159 Gamewell-FCI Approved, UL Listed compatible addressable
monitor/control devices per signaling line circuit (ILI-MB-E3 or ILI-S-E3 only)
Accommodates 126 Gamewell-FCI Approved, UL Listed compatible sensors/modules
per signaling line circuit (ILI95-MB-E3 or ILI95-S-E3 only)
80-character alphanumeric LCD display (40 characters user-defined)
4100 event history buffer (non-volatile)
Power-limited
Resettable/non-resettable 2.0 amp @ 24 VDC power output each
Alarm verification
Walk test
Multi-level alarm processing
Positive Alarm Sequence (PAS) operation
NAC coding
Trouble reminder
Integral RS-232 port
ANX network interface communicates between the E3 Series fire alarm control panel and the
FocalPoint Graphic Workstation
*Style 7 operation requires System Sensor, M500X Isolator Module (ILI-MB-E3 or ILI-S-E3) or
XP95-LI Line Isolator and XP95-LIB Line Isolator Base (ILI95-MB-E3 or ILI95-S-E3).
UL
®
is a registered trademark of Underwriters Laboratories, Inc.

Table of Contents

Other manuals for Honeywell Gamewell-FCI E3 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Gamewell-FCI E3 Series and is the answer not in the manual?

Honeywell Gamewell-FCI E3 Series Specifications

General IconGeneral
BrandHoneywell
ModelGamewell-FCI E3 Series
CategorySecurity System
LanguageEnglish

Related product manuals