18 E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
System Overview Specifications
1.5.10 Battery Connection (PM-9/PM-9G)
• Supervised
• 24 VDC nominal
• Maximum battery size 55 AH (with an external battery cabinet)
• 1.7 Amp maximum battery charge current
• Non power-limited
1.5.11 City Master Box Output (ILI-MB-E3 or ILI95-MB-E3)
1.5.12 Remote Signaling Output (Polarity Reversal)
(ILI-MB-E3 or ILI95-MB-E3)
1.5.13 Releasing Service (ILI-MB-E3 or ILI95-MB-E3)
Refer to the Compatibility Addendum to Gamewell-FCI Manuals, P/N 9000-0427, Section 3 for a
list of UL Listed, compatible releasing solenoids.
Voltage: 24 VDC (Nominal) FWR
Supervisory Current: .0018 amp
Alarm Current: .510 amp (max.)
Box Trip Coil Resistance: 14.5 Ohms (max.)
Line Resistance: 35 Ohms (max.)
Supervised against Opens and Grounds
Non Power-limited
Voltage: 24 VDC (nominal) FWR
Supervisory Current: .012 amp
Alarm Current: .012 amp
Line Resistance: 2 ohms (max.)
Supervised against Opens and Grounds
Non Power-limited
Voltage: 24 VDC (Nominal) FWR
Supervisory Current: .0005 amp
Alarm Current: .700 amp (max.)
Line Resistance: 2 Ohms (max.)
Supervised against Opens and Grounds
Non Power-limited