E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10 101
Intelligent Loop Interface-Main Board Connections E3 Series System Connections
3.2.2 ILI-MB-E3 Wiring Diagram
Figure 3.2.2.1 illustrates the field wiring connections for the ILI-MB-E3 sub-assembly.
Figure 3.2.2.1 ILI-MB-E3 Wiring Diagram
1 2
3 4
NOTE: IF ONLY ONE SLC IS
USED STYLE 6 (CLASS "A")
THE UNUSED SLC TERMINALS
MUST BE JUMPERED STYLE 6
TO PREVENT LOOP FAULT
DOWNLOAD CABLE
P/N: 75267
TO PM9
CONNECTOR J1
TB6-4 RXD TO PIN 3 OF DB9
TB6-3 SUPV TO PIN 9 OF DB9
TB6-2 TXD TO PIN 2 OF DB9
TB6-1 GND TO PIN 5 OF DB9
SW2 POS 1 ON = SL1 DISABLED (OFF = SLC1 ENABLED)
SW2 POS 2 ON = SL2 DISABLED (OFF = SLC2 ENABLED)
SW2 POS 3 ON = NAC1 & 2 DISABLED (OFF = NAC1 & 2 ENABLED)
SW2 POS 4 ON = BUZZER DISABLED (OFF = BUZZER ENABLED)
SW2 POS 5 ON = RS232 115.2K BAUD (OFF = DEFINED BY CamWorks)
GND
SET FOR MUNICIPAL CKT/RELEASE OR
REVERSE POLARITY OUTPUT
MB = MUNICIPAL CKT/RELEASE
(MIDDLE & LEFT PINS OF W7 & W8)
PR = REVERSE POLARITY
(MIDDLE & RIGHT PINS OF W7 & W8)
USE CABLE P/N: 75645 (20") TO
CONNECT TO J5 SOCKET OF NEXT
ILI-MB-E3 PCB, ILI-S-E3 OR ANX
PCB IN SAME CABINET (UP TO 8
ILI-E3 SERIES PCBS OR ANX MOUNTED
IN SAME CABINET CAN BE CONNECTED)
LED1 = REC (NETWORK RECONFIGURATION)
LED2 = MRC (NETWORK RECONFIGURATION ORIGINATING FROM THIS NODE)
LED3 = DUP (NODE'S NETWORK ADRESS IS DUPLICATED AT ANOTHER NODE)
LED4 = TX (NODE IS TRANSMITTING DATA TO THE NETWORK)
LED5 = RX (NODE IS RECEIVING DATA FROM THE NETWORK)
LED6 = RST (NODE IS RESETTING)
LED7 = DG (GENERAL NETWORK FAULT)
LED8 = ALRM (ALARM CONDITION)
LED9 = SUPV (SUPERVISORY OFF-NORMAL)
LED10 = TRBL (TROUBLE CONDITION)
LED12 = GND FLT (GROUND FAULT)
ALL RELAYS RATED
AT 2.0 AMPS @ 30 VDC
RESISTIVE
NOTE: TROUBLE DRY
RELAYS CONTACTS
TRANSFER UPON ALARM,
SUPERVISORY, TROUBLE
OR SYSTEM POWER LOSS
TB3
W5
+24VDC
GND
+24VDC
PM-9/PM-9G, +24VDC (+)
OPT. MOD. (+)
OPT. MOD. (-)
876
5
1 2
3 443
2
1
5 6
7
8
9
MUNICIPAL CKT (-)
MUNICIPAL CKT (+)
NON-RESET PWR OUT
SYSTEM GROUND
SYSTEM GROUND
RESETTABLE PWR OUT
UNSUPERVISED & NON PWR-LIMITED
WHEN SET FOR MUNICIPAL CKT.
UNSUPERVISED WHEN SET FOR
REVERSE POLARITY
ON
TB4
TB5
CONNECT TO EARTH GROUND PER ARTICLE 780
OF THE NATIONAL ELECTRICAL CODE. FAILURE
TO CONNECT TO A METALLIC GROUND WATER
PIPE OR GROUND DRIVEN ROD WILL RESULT IN
LOSS OF LIGHTNING PROTECTION, REDUCED
PROTECTION AGAINST TRANSIENTS AND COULD
ADVERSELY AFFECT PROPER SYSTEM OPERATION.
PANEL NEUTRAL OR CONDUIT GROUND IS NOT
ACCEPTABLE. USE 14 AWG WIRE MINIMUM.
LEAVE W1, W2, W3,
W4 & W5 OPEN
TO RPT-E3
ARCNET
CONNECTOR
J10
TO: LCD-E3 TB1-4, ASM-16 TB1-1,
ANU-48 TB1-1, LCD-7100 TB1-2, DACT-E3 TB1-1
TO: LCD-E3 TB1-3, ASM-16 TB1-2,
ANU-48 TB1-2, LCD-7100 TB1-1, DACT-E3 TB1-2
2.0 AMPS MAX. OUT OF EACH
EXT PWR OUTPUT. NOTE:
DO NOT EXCEED 2.5 AMPS TOTAL
BOTH OUTPUTS COMBINED
PM-9/PM-9G, GND (-)
NOTE: POWER CONNECTION
FROM PM-9/PM-9G IS
NON POWER-LIMITED
GROUND FAULT
DETECTION ENABLED
(MIDDLE TO RIGHT PIN)
GROUND FAULT
DETECTION DISABLED
(MIDDLE TO LEFT PIN)
+
12
J1
9
10
ARCNET ADDRESS
SW1
1235 468 7
TB1
TB2
485A 485B RB+ GND AB+ GND MU+ MU-
MB
PR
W7
MB PR
W8
J2
1
210
9
J4
2
1
16
15
USE SWITCH SW1 TO
SET ILI-MB-E3 PCB
NETWORK ADDRESS (1 - 64)
SET TO 0 (ZERO) FOR
STANDALONE MODE
SW2
1 2 3 4 5
ENA
GFLT
DIS
W9
AUX TERM
OFF
ON
USE
FACTORY
W1
BSEL
W3
BSEL
W2
ARCNET
TERM
OFF
W4
ON
J5
10
9
2
1
4 3 2 14 3 2 1 9 8 7 6 5 1234
SLC1 CLASS "B", STYLE 4 (+)
SLC1 CLASS "B", STYLE 4 (-)
SLC1 CLASS "A", STYLE 6 (-)
SLC1 CLASS "A", STYLE 6 (+)
SLC2 CLASS "A", STYLE 6 (+)
SLC2 CLASS "A", STYLE 6 (-)
SLC2 CLASS "B", STYLE 4 (-)
SLC2 CLASS "B", STYLE 4 (+)
TROUBLE COMMON
TROUBLE NORMALLY OPEN
TROUBLE NORMALLY CLOSED
SUPV NORMALLY CLOSED
SUPV NORMALLY OPEN
SUPV COMMON
ALARM COMMON
ALARM NORMALLY OPEN
ALARM NORMALLY CLOSED
LED
9
LED
8
LED
7
LED
6
LED
5
LED
4
LED
3
LED
2
LED
1
LED11 = PWR (DC POWER GOOD)
SLC WIRE SELECTION:
UNSHIELDED, TWISTED-PAIR
18 AWG MIN. 40 OHMS MAX. WIRE
RESISTANCE PER LOOP
0.5µF MAX. CAPACITANCE
PER LOOP
NOTE:
NAC1 & NAC2
TYPICAL STYLE Y
CLASS "B" NAC,
USE 33KOHM,
1/2 W EOL RESISTOR
- OR -
TYPICAL STYLE Z
CLASS "A" NAC,
NO EOL RESISTOR
REQUIRED
NAC RATINGS (EACH):
24VDC (NOMINAL) FWR
MAX. ALARM LOAD:
2.0 AMPS PER CKT
SUPERVISED &
POWER-LIMITED
18 AWG WIRE MIN.
RS232 PORT: 15 VDC MAXIMUM
0.05 AMP MAXIMUM
UP TO 115.2 K BAUD (DEFAULT)
8 DATA BITS, 1 STOP BIT, NO PARITY
NOTE: NAC1 & NAC2 ARE RATED AS SPECIAL APPLICATION.
5678
DISABLE GROUND FAULT DETECTION CIRCUIT:
1. ON THE PM-9/PM-9G WHEN LOCATED IN THE SAME
CABINET WITH A SINGLE ILI-MB-E3 PCB.