EasyManua.ls Logo

Honeywell Gamewell-FCI E3 Series - 3.4.1 Signaling Line Circuits

Honeywell Gamewell-FCI E3 Series
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
106 E3 Series Installation/Operation Manual P/N 9000-0574:I 11/04/10
E3 Series System Connections Intelligent Loop Interface - Slave Board (ILI-S-E3) Connections
INPUT/CONTROL
MODULE
NCM-1
ILI-S-E3
B (-)
A (-) A (+)
B (+)
DOTTED LINES INDICATE CLASS A,
STYLE 6 WIRING.
SMOKE/HEAT
SENSOR
3.4 Intelligent Loop Interface - Slave Board (ILI-S-E3)
Connections
3.4.1 Signaling Line Circuits
Figure 3.4.1.1 Signaling Line Circuits
The ILI-S-E3 provides two (2), 24 VDC Class A, Style
6, 7 or Class B, Style 4 signaling line circuits. See
Figure 3.4.1.1 for wiring information. Style 7 wiring
requires the use of an M500X Isolator Module, on both
sides of a device.
Wiring Instructions
SLC 1 Style 4 TB4-8 (+), TB4-7 ( - )
SLC 2 Style 4 TB4-4 (+), TB4-3 ( - )
SLC 1 Style 6 TB4-8 out, TB4-6 return
TB4-7 out, TB4-5 return
SLC-2 Style 6 TB4-4 out, TB4-4-2 return
TB4-3 out, TB4-1 return
(Polarity markings indicate the polarity that should be
maintained throughout the circuit. Polarity connected
to the circuit must be observed on all devices).
Circuit Ratings
24 VDC (nominal)
Current: 0.048 amp max. (supervisory)
0.136 amp max. (alarm)
0.100 amp max. Steady State
(short circuit)
40 Ohms max. line impedance
0.5 µf max. line capacitance
Ground fault test impedance: Zero ohms
Wiring: 18 AWG minimum, twisted-pair, unshielded
Power-limited Supervised

Table of Contents

Other manuals for Honeywell Gamewell-FCI E3 Series

Related product manuals