E3 Series Installation/Operation Manual P/N 9000-0574:I 11/04/10 119
Addressable Node Expander (ANX) Connections E3 Series System Connections
3.7.6.2 ANX-SR Wiring Diagram
Figure 3.7.6.2.1 illustrates the field wiring connections for the ANX-SR sub-assembly.
Figure 3.7.6.2.1 ANX-SR Wiring Diagram
TB2
COM A IN
COM B IN
COM A OUT TO NGA TB1-3
COM B OUT TO NGA TB1-4
LEAVE W1, W2, W3,
W4 & W5 OPEN
NOTE: POWER CONNECTION
FROM PM-9/PM-9G IS NON
POWER-LIMITED
J2
1
210
9
J4
2
1
16
15
ARCNET
TERM
OFF
W4
ON
J5
10
9
2
1
ARCNET ADDRESS
SW1
1235 468 7
43
2
1
A
B A B
1 2
3 4
GND
+24VDC
GND
+24VDC
TB1
1
2
3 4
GND
+24VDC
GND
+24VDC
TB3
RS232
RS232
BSEL
W2
BSEL
W3
W1
USE
FACTORY

SW2
ON
1 2 3 4 5
LED
1
LED
2
LED
3
LED
4
LED
5
LED
6
LED
7


 
LED KEY
LED1 = REC (NETWORK RECONFIGURATION)
LED2 = MRC (NETWORK RECONFIGURATION ORIGINATING FROM THIS NODE)
LED3 = DUP (NODE’S NETWORK ADDRESS IS DUPLICATED AT ANOTHER NODE)
LED4 = TX (NODE IS TRANSMITTING DATA TO THE NETWORK)
LED5 = RX (NODE IS RECEIVING DATA FROM THE NETWORK)
LED6 = RST (NODE IS RESETTING)
LED7 = DG (GENERAL NETWORK GROUND FAULT)
TO FOCALPOINT GATEWAY
TCP/IP NETWORK OR PORT
TB3-1 GND TO PIN 5 OF DB9
TB3-2 TXD TO PIN 2 OF DB9
TB3-3 SUPV TO PIN 9 OF DB9
TB3-4 RXD TO PIN 3 OF DB9
PM-9/PM-9G, +24vdc (+)
PM-9/PM-9G GND (-)
OPT. MOD (+)
OPT MOD (-)
J1
ARCO

ARCNET LOCAL
DIFFERENTIAL
ARCNET
REPEATER
LOCAL
REPEATER
LOCAL
REPEATER
TO RPT-E3
ARCNET
CONNECTOR
J10