E3 Series Installation/Operation Manual P/N 9000-0574:I 11/04/10 163
LCD-E3 Panel Display Connections E3 Series System Connections
3.13 LCD-E3 Panel Display Connections
The LCD-E3 provides an 80-character display of system events including indicating LEDs and
control switches. It may be remotely located via a local RS-485 serial interface. The ILI-MB-E3 or
ILI95-MB-E3 will support up to six (6), LCD-E3 displays. See Table 3.13.3.1 for the field wiring
connections.
3.13.1 Specifications
The following list the electrical specifications for the LCD-E3.
Operating Voltage: 24 VDC FWR (from PM-9/PM-9G power supply)
Operating Current: 0.024 amp
Alarm Current: 0.028 amp
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93%, non-condensing at 90° F (32° C)