Function Blocks 
CARB Carbon Potential Function Block 
Revision 11    HC900 Hybrid Control Designer Function Block Reference Guide  97 
2/07     
CARB Carbon Potential Function Block 
Description 
The CARB label stands for Carbon Potential... 
 
 
 
This block is part of the 
Loops category 
Function 
A combined Carbon Probe and Temperature Probe and PID algorithm determine Carbon Potential of 
furnace atmospheres based on a Zirconia probe input. 
Input 
Probe = 
Sensor Input from AI block (0-2000 mV) 
TEMP = Temperature Input (°F or °C) from AI block 
%CO = Percent Carbon Monoxide 1 % to 100 % 
RSP = Remote Setpoint Analog Input value in Engineering Units or Percentage (0-1.5) 
FFV = Feedforward value in percentage (0 % to 100 %) The Feedforward value is multiplied by the 
Feedforward Gain, then directly summed into the output of the PID block. 
TRV = Output Track value in Percentage. Output = TRV when TRC is on.  (If control output OUT is 
connected back to the Track Value Input [TRV], then the Track Command Input [TRC] will function as an 
output hold. This may be used where input probes are undergoing burnoff.) 
TRC = Output Track Command [ON, OFF] On – Enables TRV (Mode = Local Override) 
BIAS = Remote Bias value for Ratio PID 
SWI = Switch Inputs (from LPSW function block) 
  0 = No Change 
  1 = Initiate Autotuning 
  2 = Change Control Action (reverse to direct acting or direct to reverse acting) 
  4 = Force Bumpless Transfer 
  8 = Switch to Tune Set 1 
  16 = Switch to Tune Set 2