Function Blocks
DC Device Control Function Block
124 HC900 Hybrid Control Designer Function Block Reference Guide Revision 11
2/07
Block properties
Double click on the function block to access the function block properties dialog box.
Configuration parameters
Table 39 Device control function block parameters
Properties Group Parameter Index # Parameter Description Value or Selection
Tag Name
N/A 16-character tag name
Display
Descriptor
N/A Block description
16 characters maximum
On Delay
Time (sec)
1
Starting Time – time delay
between RUN request and
Output ON.
This parameter is configurable
from the Operator Interface.
Range: 0 – 99999
seconds (default 0)
Settings
Off Delay
Time (sec)
2
Stopping Time – time delay
before the Output turns OFF after
and OFF request.
This parameter is configurable
from the Operator Interface.
Range: 0 – 99999
seconds (default 0)

Table of Contents

Other manuals for Honeywell HC900

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell HC900 and is the answer not in the manual?

Honeywell HC900 Specifications

General IconGeneral
SeriesHC900
RedundancyOptional
Programming LanguageFunction Block Diagram, Ladder Logic, Structured Text
InputsAnalog, Digital
OutputsAnalog, Digital, Relay
DisplayOptional
ControlPID, Advanced Control
Power Supply24V DC or 100-240V AC
Storage Temperature-40°C to 85°C
Humidity5% to 95% non-condensing
Communication ProtocolsModbus, Ethernet

Related product manuals