Function Blocks 
AMB Auto/Manual Bias Function Block 
66    HC900 Hybrid Control Designer Function Block Reference Guide  Revision 11 
  2/07 
Start/Restart tab 
 
 
 
Table 20 AMB Start Restart tab configuration parameters 
Parameter  Index #  Parameter Description  Value or Selection 
Permitted 
Mode 
N/A 
Mode permitted for the 
initial start and power up 
mode. 
MAN Manual  
AUTO Automatic  
 
Initial Mode 
N/A  Mode at NEWSTART 
Newstart is the first scan 
cycle following the cold 
start of the controller  
MAN Manual  
AUTO Automatic  
 
Power up 
Mode 
N/A  Mode at power up 
MAN  Manual  
PREVIOUS  Same mode (auto or manual) 
 
Power Up 
Out 
N/A  Output at Power up 
FAILSAFE  Failsafe output value. 
LAST OUT  Same as at power down.  
Failsafe Out 
9  Failsafe Output Value  –5 to 105 (default 0)