Function Blocks 
PI Pulse Input 
264    HC900 Hybrid Control Designer Function Block Reference Guide  Revision 11 
  2/07 
Hints 
If it is necessary to turn off a device when the pulse counter is placed in HOLD, it is recommended that you 
also tie the source of the input HOLD signal to a DO block.  The DO block would then control the On/off 
State of the device. 
Configuration Parameters 
Table 77 Pulse Input Configuration Parameters 
Properties Group  Parameter  Index #  Description  Value or Selection 
Block Order N/A 
Execution Order for 
Block. 
Read Only. To change 
block order, right-click on a 
Function Block and select 
Execution Order. 
Address Rack  0 
This is the rack 
address of the PFQ 
module.  
Enter a value: from 1 to 5. 
 Module 0 
Module address of 
the PFQ module. 
Enter a value: from 1 to 
12. 
 Channel 0 
Channel on selected 
Module.  
Enter a value: from 1 to 4 
Pulse Weight  Pulses per EU  1 
Example: if 
measuring gallons 
and if 100 pulses = 1 
gallon, enter 100. 
 
Rate Sample Time 5 
The output RATE is 
calculated by 
counting number of 
pulses per Sample 
Time and scaling it to 
EU/Time Period. 
Sample Time is a 
rolling window of 
time (updated each 
scan cycle) used to 
count pulses. The 
longer the Sample 
Time the smoother 
the rate output and 
the longer it will take 
to change; the 
smaller the Sample 
Time the noisier the 
rate output but the 
quicker the 
response. 
Enter 0-60 seconds using 
0.5 sec. intervals. 
 Time Period 6 
Time unit used to 
scale the rate from 
pulses per Sample 
Time to: 
EU per Second, or 
Select Per Second, Per 
Minute, Per Hour